A bypass is needed when a vertical multistage pump can continue running below the selected model's minimum flow. Check the actual duty and control sequence; do not assume a universal bypass percentage.

Why does minimum flow matter?

Low flow can heat liquid inside the pump and reduce seal cooling. Use the selected model's flow and liquid-temperature limits.

When should a bypass be considered?

Check whether downstream valves can close while the pump runs, or whether a drive holds it at low demand. Compare actual flow through the pump with the model's minimum.

Where should bypass liquid return?

Return it to a suitable tank or source. Avoid a short loop of warm liquid straight into the suction. Verify the return line, valves and controls.

What should a selection request include?

Send the operating details with the proposed arrangement. Review the product catalog, service guidance and contact page for support. product catalog, service guidance, contact DFIN.

  1. Pump model or duty point and liquid temperature.
  2. Minimum demand, control method and low-demand run time.
  3. Suction source, return destination and piping sketch.

FAQ

Can a variable-speed drive replace a bypass?

Only if the controls keep flow within the selected model's limits or stop the pump in time.

Can the bypass return directly to suction?

Only after checking inlet temperature and suction conditions for the selected pump.